FNET
FNET (Frequency monitoring Network; a.k.a. FNET/GridEye, GridEye) is a wide-area power system frequency measurement system. Using a type of phasor measurement unit (PMU) known as a frequency disturbance recorder (FDR), FNET/GridEye is able to measure the power system frequency, voltage, and angle very accurately. These measurements can then be used to study various power system phenomena, and may play an important role in the development of future smart grid technologies. The FNET/GridEye system is currently operated by the Power Information Technology Laboratory at the University of Tennessee (UTK) in Knoxville, Tennessee, and Oak Ridge National Laboratory (ORNL) in Oak Ridge, Tennessee.
FNET (Frequency monitoring Network; a.k.a. FNET/GridEye, GridEye) is a wide-area power system frequency measurement system. Using a type of phasor measurement unit (PMU) known as a frequency disturbance recorder (FDR), FNET/GridEye is able to measure the power system frequency, voltage, and angle very accurately. These measurements can then be used to study various power system phenomena, and may play an important role in the development of future smart grid technologies. The FNET/GridEye system is currently operated by the Power Information Technology Laboratory at the University of Tennessee (UTK) in Knoxville, Tennessee, and Oak Ridge National Laboratory (ORNL) in Oak Ridge, Tennessee. ==System architecture== Currently, FNET/GridEye collects data from over 300 FDRs, most of which are installed in the North American power grid. About 70 of these units are located in 30 of the other largest grids around the world. The FDRs transmit their measurements over the Internet to phasor data concentrators (PDCs) located at the University of Tennessee and Oak Ridge National Lab. These PDCs collect more than 4 GB of phasor data per day. The PDCs also forward data to an application server that performs near-real-time analysis of the data. Examples of the analysis applications are given below. ==Applications== A variety of applications have been developed using the FNET/GridEye platform. Some operate in near-real-time, while others are used for offline analysis. ===On-line trip detection=== Line trip is one of the general disturbances in the power system. The outage of transmission lines affects the frequency and voltage stabilities of the system. By utilizing the measurement data in FNET system, the line trip events can be detected correctly and efficiently. The current project primarily focuses on the design of a professional line trip adaptor to realize the online line trip detection and to provide automatic alert notification for the clients. ===Off grid/islanding detection=== Based on the measurement data acquired by the FDRs deployed in the North American power grids, an islanding detection method is proposed and implemented. This method monitors the critical electrical loads and detects the transition of these loads from an on-grid operation to an islanding operation and also the transition from islanding back to on-grid operation. ==See also== Electric power transmission Frequency estimation Phasor (sine waves) Phasor measurement unit Utility frequency Smart Grid Global Positioning System Wide area synchronous grid ==References== ==External links== FNET Website North American Synchrophasor Initiative (NASPI)
References
- ^ D. Zhou; Y. Liu; J. Dong, "Frequency-based real-time line trip detection and alarm trigger development," 2014 IEEE PES General Meeting, pp.1-5, 27–31 July 2014 Wikipedia revision 1321450641, retrieved 2026-11-18 · 1794956400.0
- ^ Z. Lin, T. Xia, Y. Ye, Y. Zhang, L. Chen, Y. Liu, K. Tomsovic, T. Bilke, and F. Wen, "Application of wide area measurement systems to islanding detection of bulk power systems," IEEE Trans. on Power Systems, vol. 28, no. 2, pp. 2006-2015, May. 2013. Wikipedia revision 1321450641, retrieved 2026-11-18 · 1794956400.0
- ^ J. Guo, Y. Zhang, M. A. Young, M. J. Till, A. Dimitrovski, Y. Liu, and P. Williging, “Design and Implementation of a Real-Time Off-Grid Operation Detection Tool from a Wide-Area Measurements Perspective”, IEEE Trans. Smart Grid, vol.6, no.4, pp. 2080-2087, 2015. Wikipedia revision 1321450641, retrieved 2026-11-18 · 1794956400.0
- ^ a b c Zhian Zhong; Chunchun Xu; Billian, B.J.; Li Zhang; Tsai, S.-J.S.; Conners, R.W.; Centeno, V.A.; Phadke, A.G.; Yilu Liu; "Power system frequency monitoring network (FNET) implementation," Power Systems, IEEE Transactions on , vol.20, no.4, pp. 1914- 1921, Nov. 2005. Wikipedia revision 1321450641, retrieved 2026-11-18 · 1794956400.0
- ^ You, Shutang; Guo, Jiahui; Kou, Gefei; Liu, Yong; Liu, Yilu (1 May 2016). "Oscillation mode identification based on wide-area ambient measurements using multivariate empirical mode decomposition" . Electric Power Systems Research . 134 : 158– 166. doi : 10.1016/j.epsr.2016.01.012 . Wikipedia revision 1321450641, retrieved 2026-11-18 · 1794956400.0
- ^ You, Shutang; Guo, Jiahui; Wenxuan Yao; Siqi Wang; Liu, Yong; Liu, Yilu (2016). "Ring-down oscillation mode identification using multivariate Empirical Mode Decomposition". 2016 IEEE Power and Energy Society General Meeting (PESGM) . pp. 1– 5. doi : 10.1109/PESGM.2016.7742032 . ISBN 978-1-5090-4168-8 . S2CID 42808692 . Wikipedia revision 1321450641, retrieved 2026-11-18 · 1794956400.0
- ^ Gardner, R.M.; Wang, J.K.; Yilu Liu, "Power system event location analysis using wide-area measurements," Power Engineering Society General Meeting, 2006 . IEEE, vol., no., pp.7 pp., 0-0 0 Wikipedia revision 1321450641, retrieved 2026-11-18 · 1794956400.0
- ^ FNET Website Wikipedia revision 1321450641, retrieved 2026-11-18 · 1794956400.0
- ^ "NASPI Responses Summary to Questionnaire on PMU Installation and Maintenance" . Archived from the original on 2011-07-27 . Retrieved 2010-05-29 . Wikipedia revision 1321450641, retrieved 2026-11-18 · 1275087600.0
- ^ NSF Award Information Wikipedia revision 1321450641, retrieved 2026-11-18 · 1794956400.0
- ^ Phadke, A.G.; Thorp, J.S., "History and Applications of Phasor Measurements," Power Systems Conference and Exposition, 2006 . PSCE '06. 2006 IEEE PES, vol., no., pp.331-335, Oct. 29 2006-Nov. 1 2006. Wikipedia revision 1321450641, retrieved 2026-11-18 · 1794956400.0
- ^ a b Y. Zhang, P. Markham, et al ., "Wide-Area Frequency Monitoring Network (FNET) Architecture and Applications," IEEE Trans. on Smart Grid , vol. 1, no. 2, Sept. 2010, pp. 159-167. Wikipedia revision 1321450641, retrieved 2026-11-18 · 1794956400.0